8763230-216-229-B1
2
© 2007 Schneider Electric. All Rights Reserved.
Use
Local Operation on the UMI
Entering Parameter and Protection
Settings
DE51570
Data Entry Principles
Follow these steps to modify parameter or protection settings using the Sepam™
UMI:
1 Enter the proper password for either the protection or the parameter settings
(see "Entering Passwords", page 82).
2 Display the screen with the value you want to modify (see "Displaying operating
Information", page 83).
3 Modify the values using one of the three entry methods offered, depending on
the type of parameter or protection settings:
b entering Boolean values
b selecting a value from a number of options
b entering numerical values
4 Final confirmation of all the new parameter or protection settings for use by
Sepam™.
General Parameters Screen
DE51571
Entering Boolean Values
The Sepam™ display shows Boolean parameters and protection settings as two
buttons, representing the two status conditions of Boolean data. For example, the
language used for the operating texts on the Sepam™ UMI is a Boolean parameter
that can have one of two states:
b UK English
b US English as the local language
Use the following process to modify the value of a Boolean parameter or protection
setting:
1 Position the cursor by pressing or as needed.
2 Confirm the selection by pressing .
Selecting Values From a List of Options
Certain parameters and protection settings must be selected from a list of
possibilities. For example, the type of tripping curve for the "phase overcurrent"
protection function is selected from among 16 predefined curves (such as, DT, SIT,
VIT, EIT, etc.).
Perform the following steps to select a particular parameter or protection setting:
:
1 Press or as needed to position the cursor on the value you want to
modify.
2 Press to confirm your value selection.
3 Press or to scroll through the possibilities.
4 Press to confirm the new value.
Entering Numerical Values
The Sepam™ display shows numerical parameters and protection settings as three
digits, with or without the decimal point and the unit symbol.
To modify the value of a numerical parameter or protection setting, follow these
steps:
1 Press or as needed to position the cursor on the value you want to
modify.
2 Press to position the cursor on the first digit.
3 Use or as needed to scroll through the character list. The available
characters are the digits from 0 to 9, the decimal point, and a space.
4 Press again to confirm your choice and proceed to the next digit. After
confirming the third digit, the cursor positions on the unit symbol.
5 Use or as needed to scroll through the available units.
6 Press to confirm unit selection.
Setting screen for the "phase overcurrent" protection function
(ANSI 50/51)
1. Boolean setting
2. Selection of a value among a number of options
3. Numerical value
4. Boxes for final validation (Apply) or to cancel (Cancel) the
procedure
5. Pictogram indicating that the user is authorized to modify
parameters and protection settings (after entry of the
parameter-setting password)