Installation
1A/5A Current Transformers
Restricted Ground Fault Differential Protection (ANSI 64REF)
b The primary current of the neutral point current transformer used must comply
with the following rule:
0.1 I
N ≤ Neutral Point CT Primary Current ≤ 2 IN
where IN = primary current of phase CTs on the same winding
Current transformers should be defined by the equation below that produces the
highest knee-point voltage:
Vk ≥ (R
CT
+ RW) x 20 IN
Vk ≥ (R
CT
+ Rw) (1.6 I
3P
/IN) x IN
Vk ≥ (R
CT
+ Rw) (2.4 I
1P
/IN) x IN
The equations apply to the phase current transformers and the neutral-point current
tranformer, where
IN is the CT rated secondary current.
RCT is the CT internal resistance.
Rw is the resistance of the CT load and wiring.
I3P is the maximum current value for a three-phase short circuit.
I1P is the maximum current value for a phase-to-ground short circuit.
CCA630/CCA634 Connector
DE80051
Function
The current transformers (1A or 5A) are connected to the CCA630 or CCA634
connector on the rear panel of Sepam™:
b The CCA630 connector connects three phase current transformers to
Sepam™.
b The CCA634 connector connects three phase current transformers and
one zero sequence current transformer to Sepam™.
The CCA630 and CCA634 connectors contain interposing ring CTs with through
primaries. When measuring phase and zero sequence currents, these primaries
provide impedance matching and isolation between the 1A or 5A circuits and
Sepam™.
The connectors can be disconnected with the power on since disconnection does
not open the CT secondary circuit.
DE80059
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
b Only qualified electrical workers should install this equipment.
Such work should only be performed after reading this entire set
of instructions.
b NEVER work alone.
b Before performing visual inspections, tests, or maintenance on
this equipment, disconnect all sources of electric power. Assume
that all circuits are live until they have been completely de-
energized, tested, and tagged. Pay particular attention to the
design of the power system. Consider all sources of power,
including the possibility of backfeeding.
b Always use a properly rated voltage sensing device to confirm
that all power is off.
b Disconnect the Sepam™ unit current inputs by unplugging the
CCA630 or CCA634 connector. Do not disconnect the wires from
it. The CCA630 and CCA634 connectors ensure continuity of the
current transformer secondary circuits.
b Short-circuit the current transformer secondary circuits before
disconnecting the wires connected to the CCA630 or CCA634
connector.
Failure to follow these instructions will result in death or serious
injury.