
41
1
© 2007 Schneider Electric. All Rights Reserved.
63230-216-229-B1
Installation
ACE990 Zero Sequence
CT Interface
Connection
DE51682
Connecting a Zero Sequence CT
Connect only one zero sequence CT to the ACE990 interface.
The secondary circuit of the MV zero sequence CT connects to two of the five
ACE990 interface input terminals. To define the two input terminals, you must know:
b Zero sequence CT ratio (1/n)
b Zero sequence CT power
b Close approximation of rated current INr
(INr is a general setting in Sepam™ and defines the ground fault protection
setting
range between 0.1 and 15 INr)
The table below is used to determine:
b the two ACE990 input terminals to connect to the MV zero sequence CT
secondary
b the type of residual current sensor to set
b the exact value of the rated residual current INr setting, given by the following
formula: INr = k x number of zero sequence CT turns
with k the factor defined in the table below
The zero sequence CT must connect to the interface in the right direction for correct
operation. The MV zero sequence CT secondary output terminal S1 must connect
to the terminal with the lowest index (Ex).
K Value ACE990 Input
Terminals to be
Connected
Residual Current
Sensor Setting
Min. MV Zero
Sequence CT
Power
Example:
Given a zero sequence CT with a ratio of 1/400 2 VA, used
within a measurement range of 0.5 A to 60 A.
How should it be connected to Sepam™ via the ACE990?
1. Choose a close approximation of the rated current In0,
5 A.
2. Calculate the ratio:
approx. In0/number of turns = 5/400 = 0.0125.
3. Find the closest value of k in the table opposite to
k = 0.01136.
4. Check the mininum power required for the zero sequence
CT:
2 VA zero sequence CT > 0.1 VA V OK.
5. Connect the zero sequence CT secondary to ACE990 input
terminals E2 and E4.
6. Set Sepam™ up with:
I
Nr = 0.0136 x 400 = 4.5 A.
This value of In0 can be used to monitor current between
0.45 A and 67.5 A.
Wiring of MV zero sequence CT secondary circuit:
b MV zero sequence CT S1 output to ACE990 E2 input
terminal
b MV zero sequence CT S2 output to ACE990 E4 input
terminal.
0.00578 E1 - E5 ACE990 - range 1 0.1 VA
0.00676 E2 - E5 ACE990 - range 1 0.1 VA
0.00885 E1 - E4 ACE990 - range 1 0.1 VA
0.00909 E3 - E5 ACE990 - range 1 0.1 VA
0.01136 E2 - E4 ACE990 - range 1 0.1 VA
0.01587 E1 - E3 ACE990 - range 1 0.1 VA
0.01667 E4 - E5 ACE990 - range 1 0.1 VA
0.02000 E3 - E4 ACE990 - range 1 0.1 VA
0.02632 E2 - E3 ACE990 - range 1 0.1 VA
0.04000 E1 - E2 ACE990 - range 1 0.2 VA
0.05780 E1 - E5 ACE990 - range 2 2.5 VA
0.06757 E2 - E5 ACE990 - range 2 2.5 VA
0.08850 E1 - E4 ACE990 - range 2 3.0 VA
0.09091 E3 - E5 ACE990 - range 2 3.0 VA
0.11364 E2 - E4 ACE990 - range 2 3.0 VA
0.15873 E1 - E3 ACE990 - range 2 4.5 VA
0.16667 E4 - E5 ACE990 - range 2 4.5 VA
0.20000 E3 - E4 ACE990 - range 2 5.5 VA
0.26316 E2 - E3 ACE990 - range 2 7.5 VA
Connection to Sepam™ Series 80
b To residual current Ir input, on connector , terminals 14 and 15 (shielding)
b To residual current I'r input, on connector , terminals 17 and 18 (shielding)
Recommended cables
b Cable between zero sequence CT and ACE990: less than 50 m (160 ft) long
b Sheathed cable shielded by tinned copper braid between the ACE990 and
Sepam™: maximum length 2 m (6.6 ft)
b Cable cross-section between 0.93 mm²
(AWG 18) and 2.5 mm² (AWG 12)
b Resistance per unit length: less than 100 mΩ/m (30.5 mΩ/ft)
b Minimum dielectric strength: 100 Vrms.
Follow these steps to connect the cable.
1 Connect the connection cable shielding in the shortest manner possible
(2 cm or 5.08 in maximum) to the shielding terminal on the Sepam™ connector.
2 Flatten the connection cable against the metal frames of the cubicle. The
connection cable shielding is already grounded in Sepam™. Do not ground the
cable by any other means.
Komentarze do niniejszej Instrukcji