Commissioning
Checking Residual Current/
Voltage Input Connections
Description
Perform this check when the residual voltage is:
1 delivered by three VTs on the secondary circuits
connected in a broken delta arrangement
2 when the residual current is obtained by a specific
sensor such as:
b CSH120 or CSH200 zero sequence CT
b CSH30 interposing ring CT (whether installed on
the secondary circuit of a single 1A or 5A CT that
encompasses the three phases, or on the neutral
connection of the three 1A or 5A phase CTs)
b other zero sequence CT connected to an
ACE990 interface
Block Diagram
Procedure
1 Connect according to the diagram below:
b the generator voltage terminals to the voltage test terminal box using the plug
provided
b a wire between the generator current terminals to inject current into the
primary circuit of the zero sequence CT or CT, with:
v the wire passing through the zero sequence CT or CT in the Pa-Pb
direction
v with P1 the bus end and P2 the cable end
2 Turn the generator on.
3 Apply a V
Ln
voltage, set to the rated secondary voltage of the VTs, connected in
a broken delta arrangement (V
LL
s / 3 or Uns/3)
4 Inject a current set to 5A in phase with the voltage applied (generator phase
displacement α(V
Ln
, I) = 0°)
DE50714
Note: the number of CTs/VTs connected to the Sepam™ current/voltage connector phase inputs is given as an example and is not used for the test.
* Detection of Plugged Connector (required for proper operation. Installed manually)
DE50359
Sepam™ Series 80 is equipped with two
independent residual current inputs which
may be connected to a zero sequence CT
installed on the cables, tank grounding
cable or neutral point of a transformer, or on
the grounding cable of a motor or generator. In some
cases, reading of the
ϕ
0 or
ϕ
’0 angle is impossible due
to the position of the zero sequence CT (for example,:
transformer tank grounding cable or neutral point) or
because only one of the two Ir or Vr measurements is
necessary or possible. When this is the case, simply
check the measured residual current value Ir or I’r.
5 Use the SFT2841 software to check the following:
b the value indicated for the measured Ir residual current is approximately
equal to 5A
b the value indicated for the measured V0 residual voltage is approximately
equal to the rated primary phase-to-neutral voltage of the VTs
(V
Ln
p = V
LL
p / 3)
b the value indicated for the phase displacement ϕr(Vr, Ir) between the Ir
current and Vr voltage is approximately equal to 0°
6 Use the same procedure if the I’r input is connected. When this is the case, the
phase displacement angle you want to check is ϕ’r(Vr, I’r), between the I’r current
and Vr voltage.
7 Turn the generator off when you finish the test.
Van
Vbn
Vcn
Vr
a
b
c
Ir
Van
Vbn Vcn
Przeglądanie stron 133