Black Box IC109A-R2 Instrukcja Instalacji Strona 145

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 164
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 144
13963230-216-229-B1
3
© 2007 Schneider Electric. All Rights Reserved.
Commissioning
Checking Optional
Module Connections
MET1482 Module
Temperature Sensor Inputs
Sepam™ T81, T82, T87, M81, M87, M88, G82, G87,
G88, and C86 units provide a temperature monitoring
function that checks the connection of each RTD that is
configured.
An RTD FAULT alarm is generated whenever one of the
RTDs is detected as being short-circuted or
disconnected (absent).
To identify faulty RTD(s):
1 Display the temperature values measured by
Sepam™ using the SFT2841 software.
2 Check the consistency of the temperatures
measured:
b the temperature displayed is "****" if the RTD is
short-circuited (T < –35 °C or T < –31° F)
b the temperature displayed is "-****" if the RTD
is disconnected (T > 205 °C or T > 401° F)
MSA141 Module Analog
Output
1 Identify the measurement associated by parameter
setting to the analog output using the SFT2841
software.
2 Simulate, if necessary, the measurement linked to
the analog output by injection.
3 Check the consistency between the value
measured by Sepam™ and the indication given by
the device connected to the analog output.
MCS025 Module Voltage Inputs
Block Diagram
DE51264
Procedure
1 Connect the single-phase voltage generator to the corresponding test terminal
box, using the plugs provided, according to the block diagram below.
2 Turn the generator on.
3 Apply a voltage V
Ln
set to the rated secondary voltage V
Ln
s sync1
(V
LL
s sync1= V
LL
s sync1 / 3) in parallel between the input terminals of the two
voltages to be synchronized.
4 Use the SFT2841 software to check that:
b the measured voltage difference dV
LL
, frequency difference dF and phase
difference d
φ values are equal to 0
b the close enable sent by the MCS025 module is received on the Sepam™
series 80 logic input assigned to this function (logic input in 1 status in the
"Input, output and LED status" screen)
5 Use the SFT2841 software to check that for the other Sepam™ Series 80 units
concerned by the "Sync-check" function the close enable sent by the MCS025
module is received on the logic input assigned to this function (logic input in 1
status in the "Input, output and LED status" screen).
6 Turn the generator off.
Przeglądanie stron 144
1 2 ... 140 141 142 143 144 145 146 147 148 149 150 ... 163 164

Komentarze do niniejszej Instrukcji

Brak uwag