35
1
© 2007 Schneider Electric. All Rights Reserved.
63230-216-229-B1
Installation
LPCT Type Current Sensors
Test Accessories
ACE917 Injection Adapter
Function
The ACE917 adapter is used to test the protection chain with a standard injection box
when Sepam™ is connected to LPCT sensors.
The ACE917 adapter is inserted between:
b the standard injection box
b the LPCT test plug is either:
v integrated in the Sepam™ CCA671 interface connector
v transferred by means of the CCA613 accessory
The following are supplied with the ACE917 injection adapter:
b power supply cord
b 3-meter (9.8 ft) cord to connect the ACE917 to the LPCT test plug on
CCA671 or CCA613
DE80065
Characteristics
Power supply 115/230 V AC
Protection by time-delayed fuse 5 mm x 20 mm
(0.2 x 0.79 in)
0.25 A rating
CCA613 Remote Test Plug
Function
The CCA613 test plug flush-mounts on the front of the cubicle. It has a 3-meter
(9.8 ft) cord that transfers data from the test plug integrated in the CCA671 interface
connector on the rear panel of Sepam™.
Dimensions
DE80045
DE80046
Front view with cover lifted Right side view
DE80047
Cut-out
in.
(mm)
(260)
10.24
(170)
6.69
(70)
2.76
in.
(mm)
(44)
1.73
(67.5)
2.66
Mounting lug
Cable
(13)
0.51
(80)
3.15
(50)
1.97
(67.5)
2.66
in.
(mm)
Komentarze do niniejszej Instrukcji