Black Box IC109A-R2 Instrukcja Instalacji Strona 74

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 164
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 73
68
© 2007 Schneider Electric. All Rights Reserved.
1
63230-216-229-B1
Installation
ACE9092
RS232/RS485 Converter
Function
PE50035
The ACE9092 converter connects a master/central computer equipped with a
V24/RS232 type serial port (as a standard feature) to stations connected to a two-
wire RS485 network.
After you set the operating parameters, the ACE9092 converter uses two-way
simplex (half-duplex, single-pair) transmission to provide conversion, network
polarization, and automatic frame dispatching between the master and the stations
without the need for any flow control signals.
The ACE9092 converter also provides a 12 V DC or 24 V DC supply voltage for the
distributed power supply of the Sepam™ ACE9492, ACE959 or ACE969 interfaces.
The communication settings should be the same as the Sepam™ and supervisor
communication settings.
ACE909-2 RS 232/RS485 Converter.
Characteristics
DANGER
Mechanical Characteristics
HAZARD OF ELECTRIC SHOCK, EXPLOSION
OR ARC FLASH
b Only qualified electrical workers should
install this equipment. Such work should
be performed only after reading this entire
set of instructions.
b NEVER work alone.
b Before performing visual inspections,
tests, or maintenance on this equipment,
disconnect all sources of electric power.
Assume that all circuits are live until they
have been completely de-energized,
tested, and tagged. Pay particular
attention to the design of the power
system. Consider all sources of power,
including the possibility of backfeeding.
b Always use a properly rated voltage
sensing device to confirm that all power is
off.
b Screw tight all terminals, even those not in
use.
Failure to follow these instructions will result
in death or serious injury.
Weight 0.280 kg (0.617 lb)
Assembly On symmetrical or asymmetrical DIN rail
Electrical Characteristics
Power supply 110 to 220 V AC ± 10%, 47 to 63 Hz
Galvanic isolation between ACE power supply
and frame, and between ACE power supply
and interface supply
2000 Vrms, 50 Hz, 1 min
Galvanic isolation
between RS 232 and RS485 interfaces
1000 Vrms, 50 Hz, 1 min
Protection by time-delayed fuse 5 mm x 20 mm
(0.2 in x 0.79 in)
1 A rating
Communication and Sepam™ Interface Distributed Supply
Data format 11 bits: 1 start, 8 data, 1 parity, 1 stop
Transmission delay < 100 ns
Distributed power supply for Sepam™
interfaces
12 V DC or 24 V DC
Maximum number of Sepam™ interfaces with
distributed supply
12
Environmental Characteristics
Operating temperature –5°C to +55°C (+23°F to +131°F)
Electromagnetic Compatibility Standard Value
Fast transient bursts, 5 ns IEC 60255-22-4 4 kV with capacitive
coupling
in common mode
2 kV with direct coupling
in common mode
1 kV with direct coupling
in differential mode
1 MHz damped oscillating wave IEC 60255-22-1 1 kV common mode
0.5 kV differential mode
1.2/50 µs impulse waves IEC 60255-5 3 kV common mode
1 kV differential mode