Use
SFT2841 Setting and Operating
Software
Configuring Sepam™
PE50590
Called Modem Configuration
The modem on the Sepam™ side is the called modem. Confugure this modem first,
either by AT commands from a PC using HyperTerminal (the configuration tool
supplied with the modem) or by setting switches (see the modem manufacturer’s
manual).
Modem RS485 Interface
The configuration parameters for the modem’s RS485 interface are defined in
accordance with the Sepam™ communication interface configuration:
b speed: 4800, 9600, 19200, or 38400 baud
b character format: 8 data bits + 1 stop bit + parity (none, even, odd)
Telephone Network Interface
Modern modems offer sophisticated features such as checking telephone line
quality, error correction, and data compression. These options are not appropriate
for communication between SFT2841 and Sepam™, which is based on the Modbus
RTU protocol. They can adversely affect communication performance.
You should pay attention to the following items:
1 Invalidate the error correction, data compression, and telephone line quality
monitoring options.
2 Use the same end-to-end communication speed between:
b the Sepam™ network and the called modem
b the called modem (Sepam™ side) and the calling modem (PC side)
b the PC and the calling modem (see recommended configurations table)
Configuration window for the communication network via
telephone modem
Sepam™ Network Telephone Network PC Modem Interface
38400 baud V34 modulation, 33600 baud 38400 baud
19200 baud V34 modulation, 19200 baud 19200 baud
9600 baud V32 modulation, 9600 baud 9600 baud
Industrial Configuration Profile
The following table shows the main characteristics of the Sepam™-side modem.
These characteristics match a configuration profile commonly known as an
"industrial profile," as opposed to the configuration of modems used in offices.
Depending on the type of modem, configuration occurs by AT commands from a PC
using HyperTerminal, a configuration tool supplied with the modem, or by switch
settings (see the modem manufacturer’s manual).
Industrial Profile Configuration Characteristics AT Command
Transmission in buffered mode, without error correction \N0 (force &Q6)
Data compression deactivated %C0
Line quality monitoring deactivated %E0
DTR signal assumed to be permanently off (allows the modem
connection to be established automatically on an incoming call)
&D0
CD signal off when carrier is present &C1
All reports made to Sepam™ blocked Q1
Character echo suppression E0
No flow control &K0