Use
Local Operation on the UMI
Operating Functions Requiring a
Password
Resetting Diagnosis Information
The Sepam™ UMI can reset certain protection functions when you enter the
parameter-setting password, such as:
b the number of starts before blocking (this is linked with the "Starts per hour"
function ANSI 66)
b heat rise calculated by the "Thermal overload" function (ANSI 49RMS)
Perform the following steps to reset the information:
1 Enter the password for parameter settings.
2 Display the screen showing the information you want to reset.
3 Press to complete the action.
DE51569
Testing Logic Outputs
You can change the status of each logic output for five seconds. The check on logic-
output connections and switchgear operation is thus simplified.
The screens on the logic outputs can be accessed in the "Sepam™ Information"
category and in the "Inputs/outputs" subcategory.
The first screen displays the logic outputs of the base unit. Up to three additional
screens present the logic outputs of any additional MES120 modules.
A "Logic Outputs" screen displays the status of all the logic outputs for a given
module. Use this screen to change the status of each output in order to check its
operation.
Perform the following steps to test a logic output:
1 Enter the password for parameter settings.
2 Display the screen showing the logic output to be tested.
3 Press to go to the selection field for the output to be tested.
4 Press the cursor keys, or , to select the desired logic output by scrolling
the addresses of the logic outputs in the module
5 Press to confirm the selected output.
6 Press or as needed to go to the [Test] box.
7 Press to change the status of the logic output for five seconds.
Screen presenting the logic outputs of the base unit and the
status of each output, with the possibility of testing each output