Maintenance
Troubleshooting Assistance
MAJOR Fault: Sepam™ is in Fail-Safe Position
b ON LED of UMI on in front
b LED of UMI on in front
or LED of DSM303 remote advanced UMI flashing
b green LED on rear panel on
b red LED on rear panel on
PE50359
Major faults are only cleared after the cause
of the fault is corrected and Sepam™ is
switched on again.
PE50139
No Connection made with SFT2841
Possible Cause Action / Remedy
Memory cartridge absent. Switch off Sepam™.
Install the memory cartridge and secure it
by tightening the two integrated screws.
Switch Sepam™ on again (see page 150).
Fault message on display:
major fault
Major internal fault. Change base unit.
Connection made with SFT2841
Possible Cause Action / Remedy
SFT2841 indicates major fault, but no missing
module: Base unit internal fault.
Change base unit.
Memory cartridge not compatible with version of
the base unit (see below).
Note the version using the SFT2841 software,
Diagnosis screen.
Contact the local support team.
The hardware configuration is incorrect or
incomplete.
Use the SFT2841 software, in connected
mode, to determine the cause.
The SFT2841 Diagnosis screen displays the
missing items in red (see table below).
Check on hardware configuration using SFT2841
Diagnosis screen Possible cause Action / remedy
CCA630, CCA634, CCA671 or
CCA640 connector in B1 or B2
position displayed in red.
Connector absent. Install a connector.
If the connector is present,
check that it is plugged in
correctly and held in place
by the two screws.
LPCT sensors not connected. Connect the LPCT sensors.
Connector in position E
displayed in red.
Connector E unplugged or no
jumper between terminals 19
and 20.
Plug in connector E.
Fit the jumper.
MES120 module in H1, H2 or
H3 position displayed in red.
MES120 module absent. Install MES120 module.
If the MES120 module is
present, check that it is
plugged in correctly and held
in place by the two screws.
If the fault is still present,
replace the module.
PE10156
Fault message displayed
if cartridge is not compatible
Rules on Compatibility Between the Cartridge and the Base
Unit
The major index of the base-unit version must be greater than or equal to the major
index of the cartridge-application version.
Example: The base unit with a version V1.05 (major index = 1) and an application
with a version V2.00 (major index = 2) are not compatible.
If this rule is not observed, a major fault occurs and Sepam™ displays the message
in the left column.