Maintenance
Replacing the Base Unit
Replacing the Battery
PE80024
Replacing the Base Unit
The memory cartridge is easily accessible and can be removed from the front of
Sepam™. It reduces the duration of maintenance operations.
Perform the following steps when a base unit fails:
1 Switch off Sepam™ and unplug connectors.
2 Remove the memory cartridge.
3 Replace the faulty base unit with a replacement unit (no memory cartridge).
4 Put the memory cartridge in the new base unit
5 Plug in the connectors.
6 Switch Sepam™ on again.
If there are no compatibility problems (see page 147), Sepam™ should operate with
all its standard and customized functions without reloading any protection and
parameter settings.
Replacing the Battery
Characteristics
Single use 1/2AA format 3.6 V, 0.8 Ah lithium battery, such as models:
b SAFT model LS14250
b SONNENSCHEIN model SL-350/S
Battery Recycling or Disposal
Refer to Environmental Protection Agency Solid Waste And Emergency Response
(5306W) EPA530-K-97-009 November 1997 for directions and guidelines for
recycling and disposal of batteries.
Replacing the Battery
1 Lift off the protective battery cover after removing both fixing screws.
2 Change the battery, being sure to use the correct type and polarity.
3 Replace the protective battery cover and both fixing screws.
4 Recycle the used battery.
Note : The battery can be replaced with Sepam™ energized.
Note : For technical support, contact (615) 287-3400 or go to www.powerlogic.com