Commissioning
Checking Input Connections
3-Phase Generator
Block Diagram: Two VTs Connected to Sepam™
DE50707
* Detection of Plugged Connector (required for proper
operation. Installed manually)
Procedure
Perform the following steps to check input connections when two or three VTs are
connected to Sepam™, as shown in the preceding two diagrams:
1 Connect the 3-phase voltage and current generator to the corresponding test
terminal boxes. Use the plugs provided, according to the appropriate diagram in
terms of the number of VTs connected to Sepam™.
2 Turn the generator on.
3 Apply the three generator voltages Van, Vbn and Vcn, balanced and set to the
rated secondary phase-to-neutral voltage of the VTs (that is, VNs = V
LL
s/3).
4 Inject the three generator currents Ia, Ib and Ic, balanced and set to the rated
secondary current of the CTs (namely, 1A or 5A) and in phase with the voltages
applied (specifically, generator phase displacement:
α1(Van, Ia) = α2(Vbn, Ib) = α3(Vcn, Ic) = 0°).
5 Use the SFT2841 software to check the following:
b the value indicated for each of the phase currents Ia, Ib, and Ic is
approximately equal to the rated primary current of the CTs
b the value indicated for each of the phase-to-neutral voltages Van, Vbn, and
Vcn is approximately equal to the rated primary phase-to-neutral voltage of
the VT
(V
Ln
p = V
LL
p/3)
b the value indicated for each phase displacement ϕa(Van, Ia), ϕb(Vbn, Ib),
and ϕc(Vcn, Ic) between currents Ia, Ib or Ic and voltages Van, Vbn,or Vcn
respectively is approximately equal to 0°
6 Turn the generator off.
a
b
c
Ia
Ib
Ic
Van
Vbn
Vcn
n
n
n
Van
Vbn Vcn